Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09OT01104
Parcel: 124090220

Address:
1714 E 8TH ST

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T09OT01104
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2009 PAUL MACHADO ENGINEERING REVIEW Approved June 5, 2009 (No Special Inspection Required).
FLOODPLAIN USE PERMIT NO. T09OT001104
ADDRESS: 1714 E. 8th Street
PROPERTY OWNER'S NAME: Laurence D Mulhern

The applicant is authorized to use a portion of the flood hazard area in the City of Tucson on the property described as (legal description):

Lot 3 of Bingham and the West 6 feet of Lot 4 in block 2 being 0.19 Acres, all in Section 7, T-14-S, R-14-E for the purpose of constructing a detached garage.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

The following conditions shall apply to this permit. (Or refer to Chapter 26 page 35)

1. All work shall conform to the attached plans (Drainage Report and all improvement plans) which are made part of this permit.

2. This parcel within a FEMA Zone AE, 100-year floodplain. Therefore, the proposed development is subject to floodplain requirements.

3. The new garage is to be constructed in a manner to prevent flotation, collapse, and lateral movement.

4. The existing drainage patterns at the property lines shall remain the same.

5. The garage must be used solely for storage, parking of vehicles, and/or building access.

6. Within 5 (five) days of issuance of this permit, through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "Construction proceeding under requirements of City of Tucson Floodplain Use Permit No. T09OT01104. For information please call 791-5550."

6. Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.

7. This permit becomes invalid and is subject to additional floodplain review, if any required development permit (s') changes the configuration of the structure and or site development.

8. No electrical is to service the garage.

9. Interior walls of garage are to remain unfinished and resistant to flood damage.

10. No machinery and equipment which service a building such as furnace, air conditioners, heat pumps, hot water heaters, washer, dryers, elevator lift equipment, electrical junction and circuit breaker boxes, and food freezers, etc. are permitted within the garage.

11. Garage to be constructed per Foundation, Framing and Elevations Plan completed by Paul Kilonzo Nzomo, P.E., Dated 05/21/09 indicating that (4) 8"x20" openings will be installed - (1) on the upstream side and (3) on the downstream side. The proposed square footage of the garage walls = 616 sf. = 616 sq. in. Each vent (8"x20") = 160 sq. in. 640 sq. in. provided.

12. Garage to have a minimum of two opening installed with a total net area of not less than one square inch for every square foot of enclosed area subject to flooding shall be provided.

a) Per submitted Site Plan and supplementary Foundation, Framing and Elevations Plan. The bottom of all (4) 8"x20" openings (called out as vents on plan) shall be no higher than one foot above interior grade.

b) Openings may be equipped with screens, louvers, valves or other coverings or devices provided that they permit the entry and exit of floodwaters.

13. See the associated activity T09CM01403.

14. Any patio and/or other walls to be constructed on site will require a separate Permit.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions set forth in this permit are not complied with. Also, this permit will expire one year from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Section.

(EXPIRATION DATE) Month: 06 Day: 05 Year: 2010

APPLICANT NAME: Laurence D Mulhern
ADDRESS: 1714 E. 8th Street
PHONE NO.: (520) 624-9829


________________________ _____
APPLICANT'S SIGNATURE DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2009 CPIERCE1 OUT TO CUSTOMER Completed