Permit Number: T09OT00460
Parcel: 123120160

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T09OT00460
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved March 12, 2009
FLOODPLAIN USE PERMIT # T09OT00460
PROJECT ADDRESS: 1434 E Hampton Street
APPLICANT'S NAME: Moody Contruction Sol. LLC - Linda Moody
PROPERTY OWNER: Frank & Misty McCormick


This parcel lies within a City of Tucson 100-year floodplain map number 040076 C 2227K, effective February 8, 1999. The applicant is authorized to use a portion of the flood hazard area in the City of Tucson, Arizona, on the property described as:

1434 E Hampton Street, Tucson, AZ 85719, A portion of parcel 123-12-0160, MONTEREY AMENDED LOT 4 & E2 OF L 5 BLK 26 (10464/123 11545/3015). In a portion of Township 14 South, Range 14 East, Section 6, for the construction of an addition to an existing non-conforming structure.


The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

The following conditions apply to this permit:

1) This permit becomes invalid and is subject to additional floodplain review, if any required development permit changes the configuration of the improvement, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from development within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.

2) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.

3) The addition is located within a City of Tucson 100-year Floodplain, as defined in The Floodplain and Erosion Hazard Management Ordinance, Chapter 26 of the Tucson Code (Ordinance).

4) Hydrology Report for Mountain Avenue Wash (JE Fuller Hydrology and Geomorphology, 30JAN08), Signed and sealed by Robert Shand (1-30-08).

5) For purposes of this permit the following flood elevations shall be used:

Base Flood Elevation (BFE) = 2414.7 feet NAVD 1988
Regulatory Flood Elevation (RFE) = 2415.7 feet NAVD 1988

Finished floor of the addition and the lowest point of any attached appliances including water heater, air conditioning units, etc. are to be at or above the Regulatory Flood Elevation (RFE).

6) Floodplain Approval of elevation certificate, prepared by an Arizona State Registered Land Surveyor, is required prior to final approval of single family residence or electrical inspection. The Elevation Certificate must include the identity and elevation of the lowest service equipment/machinery servicing the single family residence as well as the identity and location of all other equipment/machinery servicing the single family residence. All elevation certificates are to be returned to Development Services - Engineering Department at 201 N Stone on the 1st floor - for review, approval and the release for inspections.

7) Certification is required by an Arizona State Registered Professional Civil Engineer that the finished floor of the single family residence meets all the requirements of Section 26-9 of the Ordinance.

8) All work shall conform to the approved details and general Site Plan, which are made part of this permit.

9) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T09OT00460 FOR INFORMATION PLEASE CALL 791-5550."

10) This Floodplain Use Permit and plans shall be kept in a readily accessible location on site at all times.

11) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.

12) Contractor will need to call for floodplain use permit inspections by Development Services Department Engineering Division Inspection Team (791-5550) prior to and after the installation of the prefabricated storage container.

13) See the associated activity T08CM03407.


This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit. Also, this permit will expire one year from its date of approval. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Division.

(EXPIRATION DATE) Month: 03 Day: 12 Year: 2010

APPLICANT: Moody Construction Sol. LLC - Linda Moody
ADDRESS: 1928 W Paseo Cuenca, Tucson, Arizona 85704
PHONE: (520) 240-6080
OWNER: Frank & Misty McCormick
ADDRESS: 1434 E Hampton Street, Tucson, Arizona 85719
PHONE:


SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
03/12/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved The BFE and RFE have been changed on the FUP per calculation sheet prepared by Ms Ramirez, Sheet A7 of the approved site plan and Floodplain Keynote #2 and another calculation of the HH study by JG.

Correct BFE is 2413.7 NAVD88 and RFE is 2414.7 NAVD88.
New ELCERTs have been prepared and re-issued.

RFE was used for the BFE in elevation certificate

Final Status

Task End Date Reviewer's Name Type of Review Description
04/22/2009 CINDY AGUILAR OUT TO CUSTOMER Approved