Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09OT00201
Parcel: 11615077K

Review Status: Completed

Review Details: C OF O

Permit Number - T09OT00201
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2009 TERRY STEVENS ZONING REVIEW Approved
02/04/2009 JWILLIA5 BUILDING-COMMERCIAL REVIEW Approved