Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09EL02622
Parcel: 12418276B

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC

Permit Number - T09EL02622
Review Name: BILLBOARD-BLDG/ELEC
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/15/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approv-Cond 1. A description of existing light fixture and lamp to be removed and reinstalled needs to be provided, including manufacturer, model number, lamp type, number of lamps, existing lamp lumen and ballast ratings, and overall
length and width.

2) Please add at end of note 1 pp E1 "Existing fixtures are to remain on site with no other fixtures (new or used) to be installed."

3) Please provide details for light fixture mounting brackets and for supporting rigid conduits at top of billboard.

4) Please add a note #7 stating "No parts or components to be removed, installed, replaced, or reinstalled except as noted on plans."

Final Status

Task End Date Reviewer's Name Type of Review Description
01/05/2010 SUE REEVES APPROVAL SHELF Completed
01/05/2010 GERARDO BONILLA OUT TO CUSTOMER Completed