Permit Number: T09EL02553
Parcel: 10609043B

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T09EL02553
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project :3725 N Flowing Wells
Modular Bldg, New Service


Denied for following:
1. Provide fault current for service and let through.
2. Provide size of overcurrent device at panel for transformer.

Ray T Majuta
City of Tucson, DPDS
11/20/09
Ray.Majuta@tucsonaz.gov