Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T09EL00091
Parcel: 130142730

Address:
4084 E 25TH ST

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T09EL00091
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2009 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved