Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM03431
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/08/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/31/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/31/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/31/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/31/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/31/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/31/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 12/31/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 12/31/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/31/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 12/31/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/08/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |