Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Permit Number - T09CM03411
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/11/2010 | SREEVES1 | ZONING | REVIEW | Denied | Adam Smith is the reviewer He can be reached at 520-837-6951 |
| 01/11/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | SFR #2 NEED WASTEWATER CREDIT EVALUATION (5TH FLOOR). DOES NOT INCLUDE SFR UNIT #1 OR STUDIO- BUILDING #2 |
| 01/13/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 01/28/2010 | RONALD BROWN | BUILDING-RESIDENTIAL | REVIEW | Denied | ELEVATIONS 1. Specify height above grade for finished floor, windows/doors, exterior walls, rooflines, porches, chimneys, etc. ELECTRICAL 2. Bathrooms require a separate 20-amp circuit with receptacles within 3’ of the basin, E3801.6. PLUMBING PLANS 3. Plumbing shall comply with 2006 UPC with state amendments (AZ State plumbing code). The plans should reference this code, or appeal to the Building Official for alternate design approval. 4. Provide location of hose bibs and note the requirement of backflow preventers, UPC 603. 5. Provide a gas line isometric and size the supply pipe for the connected demand. Include the length of line and BTU demand for each appliance, size of each branch, total demand, and total developed length from meter to the most remote appliance on the system, UPC 1217.0 Table 12-8. 6. Designate the location, capacity and fuel type of the heating and air conditioning equipment. Verify that the existing roof framing system will accommodate the load of the new roof top mounted HVAC system. Please indicate and show where the duct work is to be installed. Inside or roof top mounted. It does not appear as there is enough ceiling height in some spaces for an interior distribution. 7. Show the condensate line and secondary for HVAC unit, M1411.3 8. Gas appliances shall comply with ARIZONA STATE PLUMBING CODE combustion air requirements or Chapter 17, 2006 IRC. Show compliance for all appliances. Confined spaces require a minimum of two 100 SQ. IN. openings, M1702.2. 9. Water heater combustion element must be mounted 18" above the finished floor of the garage as per 1307.3. OUTDOOR LIGHTING CODE 10. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style). INTERNATIONAL ENERGY CONSERVATION CODE 11. Provide a note requiring the insulation certificate shall be posted in the electrical distribution panel before final inspection, N1101.8. end of review |