Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM03408
Parcel: 13409018B

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM03408
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2010 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
01/05/2010 JASON GREEN ENGINEERING REVIEW Denied Building plan will be stamped approved with the approval of the site plan. Refer to site plan comments.
01/06/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide structural calculations for the light pole foundations.
2. Please provide stuctural calculations for all roof top mounted HVAC equipment.
3. Please provide a letter of deferred submittals to Mr. LeeRay Hanly of Tucson P and DSD Department.
4. Please provide Special Inspection Certificates for review and approval
SHEET A1.0
5. Insure a 12" strike side clearance at door number 3 as required by ICC (ANSI) 117.1, Section 404.2.3.1.
SHEET A2.0 AND DETAIL E/A5.1
6.Please provide structural calculations and support details for the exhaust hood.
SHEET S2.1
7. Provide header sizes at all three openings on the North wall as per calculations L-5 and L-6.
END OF REVIEW
01/07/2010 RONALD BROWN ZONING HC REVIEW Denied REFERENCE BUILDING FOLDER FOR COMMENTS
01/07/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
01/22/2010 ROBERT SHERRY WATER REVIEW Approved
01/25/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the gas input to the water heater (WH-1); it is scheduled as 120 MBH input on sheet P1.0 and 199.9 MBH on sheet P5.0. Reference: Section 103.2.3, UPC 2006.
2. Provide detail 20/A6.0 referenced on detail 2/P6.0 and indicate the
3. Hub drains are not approved for use under the UPC; they do not comply with Sections 411.1 and 804.1, UPC 2006.
4. The branch piping size called out for the urinal flush valve will result in a water velocity greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Section A 6.1, UPC 2006 and Section 2.6, IS 3-2003.
5. Include the water demand (e.g. ice makers, beverage dispensers, etc.) from the filtered water system with the water calculations. Reference: Section 610.1, UPC 2006.
6. Appliances (e.g. coffee makers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or have integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Indicate how backflow protection will be provided for each appliance. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
7. The rim elevation of the next upstream sanitary manhole (2656.00) is higher than the first floor elevation (2654.70). Provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.
8. Provide a protecting vent for each fixture (e.g. floor drains). Reference: Section 901.0, UPC 2006.
9. Provide a vent for the gravity grease interceptor. Reference: Section 1009.4, UPC 2006.
10. Clarify the need for a vented flow control device for a gravity grease interceptor. Unless the manufacturer of the interceptor requires one, a flow control device in this application would be an obstruction to flow. Reference: Sections 311.5 and 1014.3.3.1, UPC 2006.
01/26/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for the building envelope. Reference: Section 101.4, International Energy Conservation Code 2006.
2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
3. Provide calculations demonstrating adequate ventilation. Reference: Section 401.2, IMC 2006.
4. Provide information to show that the exhaust fan for the Type I hood starts automatically when cooking operations commence. Reference: Section 507.2.1.1, IMC 2006.
5. Provide structural calculations and details to show that the Type I hood is supported from the building structure (i.e. how do the all-thread rods attach to the building structure) in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
6. Show that the roof top air-conditioning units supplying make up air for the kitchen hood are electrically interlocked to the exhaust fans. Reference: Section 508.1, IMC 2006.
01/28/2010 GERRY KOZIOL WWM REVIEW Denied need 5th floor credit evaluation
01/29/2010 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Electric plans denied for the following:

1. Provide onformation on electric details for Type I Hood showing automatic startup when cooking operations begin per IMC 2006 507.2.1.1. See Mechanical reviewer comments.

Rich Jiroudek
Electric Plns Exmn
520-954-0161
02/02/2010 TERRY STEVENS ZONING REVIEW Denied 02/02/2010

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
12/30/2009 DAVE MANN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/05/2010 CPIERCE1 OUT TO CUSTOMER Completed
02/05/2010 SUE REEVES REJECT SHELF Completed