Permit Number: T09CM03402
Parcel: 12217365A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM03402
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2010 GERRY KOZIOL WWM REVIEW Approved
12/28/2009 LOREN MAKUS ENGINEERING REVIEW Approved
12/28/2009 STEVE SHIELDS ZONING REVIEW Approved
12/31/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project; T09CM03402
Triplex
3127 E Adams St,
Electrical plans denied for the following;

1. Provide fault current at service and let through to panels.
2.Load calculations partly per commercial(receptacles), do per residential,also include dish/disp on load calc's.
3.Water Heater cb's to be 30amp
4.Circuit A-20 in wh room, not in panel.
5.In all 3 units 3 appliance units are used, apply 3 appliance circuits in load calculations.
6. GFI circuits in bathrooms to be used only on bath receptacles.
7.Circuit B-10 used for a receptacle bt panel,used as water heater in pnl, also not in plan.
8.Show panel N and id circuits in plan,mark GFI.
9. Units to be as numbers not letters,show on application.
Electrical plans need to be re-reviewed entirely.

Ray T Majaauta
PDSD, C of T'
Elect Plan Ck
12/31/09
Ray.Majuta@tucsonaz.gov
12/31/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/31/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/31/2009 ROBERT SHERRY WATER REVIEW Approved
12/31/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/31/2009 MARTIN BROWN FIRE REVIEW Approved
12/31/2009 ERIC NEWCOMB ADA REVIEW Passed
12/31/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/31/2009 ERIC NEWCOMB ZONING HC REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2010 CPIERCE1 OUT TO CUSTOMER Completed