Permit Number: T09CM03398
Parcel: 13316030G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM03398
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/29/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT: 6325 E TANQUE VERDE, T09CM03398

THE ELECTRICAL PLANS HAVE BEEN DENIED FOR THE FOLLOWING;

1.THE EQUIPMENT GROUND FOR THE CIRCUIT TAPPED IS AFTER A 1000 AMP DISCONNECT, THE GROUNG CONDUCTOR IS TO BE SIZED PER NEC 250-122.
2. THE NEW TAP SHOULD BE COMING OF A SPARE DISCONNECT IN THE SWITCHGEAR, SINCE THERE ARE SPARE DISCONNECTS.
3. SHEET E-3, IDENTIFY THE DISCONNECT AFTER THE TAP AND INDICATE OVERCURRENT PROTECTION SIZE.
4. SHEET E-3, NOTE 3, NOT SHOWN ON PLAN.
5. NOTE 9 APPEARES TO BE NOTE 39 ON PLAN.

RAY T MAJUTA,
PDSD,CITY OF TUCSON,
12/29/09,
ELECT PLAN CK
Ray.Majuta@tucsonaz.gov
12/29/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2010 DELMA ROBEY OUT TO CUSTOMER Completed