Permit Number: T09CM03392
Parcel: 13403021C

Address:
9066 E 20TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM03392
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2010 SEPTIC APPROVAL WWM REVIEW Denied NEED TO PROVIDE RECORDS OF EXSISTING SEPTIC SYSTEM FOR SEPTIC REVIEW
01/26/2010 RONALD BROWN BUILDING-RESIDENTIAL REVIEW Denied GENERAL
1. Please change the plumbing code reference on sheet A-1 to the 2006 UPC.
SITE PLAN
2. Specify overhead or underground electrical service.
FLOOR PLAN
3. Identify ceiling heights in all areas. Note average height at sloped ceiling areas, R305.1.
4. Show the location of attic access min. 22"x30", R807.
5. For all doors and windows, please show location and size, types, and designate the operable portion of windows.
FOUNDATION PLANS
6. Provide a note for termite treatment, R320 as amended.
7. Note grade away from foundations shall fall min 6" within the first 10’, R401.3.
8. Cross-reference all details to the foundation plans.
ELEVATIONS
9. Specify height above grade for finished floor, windows,
doors, exterior walls, rooflines, porches, chimneys, etc.
10. For thin-coat stucco systems, indicate the ICBO #, system name, and vapor barrier, R703.6.
11. Specify roof slope and roofing type, grade of materials, and method of installation, R905. For Shingle Roofing: two-layer underlayment for low-slope (2:12 to 4:12), R905.2.7.
SECTIONS - DETAILS
12. Provide 6" separation of untreated posts or columns above finished grade and 1" above concrete, R319.1.4.
13. Provide a minimum opening of 22" by 30" for access and ventilation between over-framed assemblies (>30 S.F.), R807.
14. Specify wall and ceiling covering. Note: Ceiling gypsum board must be either 5/8" or ½" sag resistant when applied to ceilings framed at 24" o/c, IRC table R702.3.5 footnote d.
ELECTRICAL PLANS
15. Provide an electrical riser diagram with grounding method and bonding to metallic piping, E3303, E3507.
16. Gas lines shall not be used as the primary grounding method, E3508.
17. Provide riser diagrams for sub-panels with feeder conductors, conduit sizes, and over-current protection (with appropriate correction factors), E3605.5.
18. TEP requires a 2½" diameter service conduit, TEP SR-305.
19. Provide equipment rated for 22,000 AIC short circuit protection when the underground cable length is less than 45 feet, 2006 Electric Service Requirements TEP SR-510.
20. Provide feeder load calculations for sub-panels (40% demand factor may not be applied), E3604.3.
21. Provide a panel schedule: panel size, circuit numbers, ampacity, and wire sizes, E3304.11, E3606.2.
22. Show the location of the panel with a 30”W x 36”D clear working space, E3305.2, E3501.6.2.
23. Note that light fixtures in clothes closets shall be installed in accordance with E3903.11.
24. Bedroom outlets shall be arc-fault protected (receptacles, lights, and smoke detectors), E3802.12.
MECHANICAL PLANS
25. Provide location of return air ducts and register sizes, M1602.
26. Show supply and return ducts with minimum R-8 insulation, R1103.2.1.
27. Designate the location, capacity and fuel type of the heating and air conditioning equipment. Designate the locations of each supply register, return air grill and all ductwork.
28. Provide an equipment specification list, M1302.1.
a. Is the size of the existing HVAC system adequate to serve the added space?
OUTDOOR LIGHTING CODE
29. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.
30. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).
INTERNATIONAL ENERGY CONSERVATION CODE
31. Provide a note requiring the insulation certificate shall be posted in the electrical distribution panel
before final inspection, N1101.8.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
02/16/2010 DELMA ROBEY OUT TO CUSTOMER Completed
02/16/2010 SUE REEVES REJECT SHELF Completed