Permit Number: T09CM03389
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03389
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/24/2009 TERRY STEVENS ZONING REVIEW Approved
12/24/2009 PAUL MACHADO ENGINEERING REVIEW Approved
12/24/2009 ERIC NEWCOMB ADA REVIEW Passed
12/24/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review 1. SHEET M-3; DETAIL 111: NOTE AT 1/2" ALL THREAD RODS REFERS TO STRUCTURAL DRAWINGS. NO STRUCTURAL DRAWINGS ARE INCLUDED IN THIS REVIEW. PROVIDE DETAIL.
2. GENERAL: ARE THE NEW UNITS ON THE ROOF HEAVIER THAN EXISTING UNITS? IF SO, PROVIDE STRUCTURAL CALCULATIONS TO INDICATE THAT THE EXISTING ROOF CAN SUPPORT THE NEW LOADS.
12/24/2009 ERIC NEWCOMB ZONING HC REVIEW Needs Review
12/24/2009 MARTIN BROWN FIRE REVIEW Approved
12/24/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/30/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the fan coil is connected to the building structure.
2. Provide a design for interlocking the exhaust fans to the heat pump.
12/30/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 5151 E Broadway Bl
T09CM03389
Office TI 5842 Sq Ft

The electrical plans have been denied for the following:

1. Sheet E-4 shows the feed for AC-1in Pnl L(1,3), also Sheet E-2 shows AC-1 in the IT room, however Sheet M-3 lists a split system(FC-1,CU-1) for the IT room. The CU-1 unit is listed at 208v 1 phase at 14.8 FLA, the FC-1 unit is listed at 460v 3 phase 22.9 FLA, clearify or correct.
2. Sheet E- Pnl H shows a new 60/3 cb feeding the new 45kva transformer, then feeding Pnl WPA. Sheet E-4 shows a 125 amp 3p cb feeding Pnl L1 via the new 45kva transformer. Also the conductors in Pnl H show #1 conductors , they should be a 60 amp with # 6 conductors.
3. Circuit L 24 is in the panel schedule not on the power plan, feeding receptacles.


Ray T Majuta
PDSD, Cof Tucson
Elect Pln Ck
12/30/09
Ray.Majuta@tucsonaz.gov
12/30/2009 ROBERT SHERRY WATER REVIEW Approved
12/30/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the sizes for the water pipe branches serving the flush valves and the connection sizes (e.g. 3/4" for the water closets and 1" for the urinal)
12/30/2009 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/14/2010 DELMA ROBEY OUT TO CUSTOMER Completed
01/14/2010 SUE REEVES REJECT SHELF Completed