Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T09CM03359
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2010 | BRIAN HEFFERNAN | COMMUNICATIONS | REVIEW | Approved | |
| 01/13/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/20/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T09CM03359 2190 E Benson Hy Cell Site The electrical plans have been denied for the following: 1.Sheet E-1 shows an overhead power drop to this new meter, City of Tucson requires all new services be underground, unless a waiver is issued. Please clarify this. 2.There appears to be other equipment on this site, is there another service powering this equipment? 3. If another service is on site , how does this new service comply with 2005 NEC sections, 230.2, 230.40 and 230.72 ? Ray T Majuta PSDS, City of Tucson, Elect Pln Ck 1/25/10 Ray.Majuta@tucsonaz.gov |
| 12/24/2009 | Michael Wyneken | PLANNING-CITY HALL | REVIEW | Approved | |
| 12/24/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/29/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 01/29/2010 | SUE REEVES | REJECT SHELF | Completed |