Permit Number: T09CM03356
Parcel: 124050630

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03356
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2009 STEVE SHIELDS ZONING REVIEW Approved
12/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/21/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical Plan Ck:T09cm03356 Yogurt Shop

1. Correct circuit breaker in panel for water heater.
2. Provide cut sheet on water heater.

Ray T Majuta,Elect Plan Ck, 12/21/09,837/4988
12/21/2009 ROBERT SHERRY WATER REVIEW Approved
12/21/2009 DAVE MANN FIRE REVIEW Approved
12/21/2009 PAUL MACHADO ENGINEERING REVIEW Approved
12/21/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a drinking fountain
2. Provide specifications and a plumbing diagram for the water heater.
12/22/2009 CPIERCE1 WWM REVIEW Needs Review
12/22/2009 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
12/22/2009 CPIERCE1 ADA REVIEW Needs Review
12/22/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/22/2009 CPIERCE1 ZONING HC REVIEW Needs Review