Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM03348
Parcel: 136244500

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03348
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2010 GERRY KOZIOL WWM REVIEW Approved
12/18/2009 STEVE SHIELDS ZONING REVIEW Approved
12/18/2009 ROBERT SHERRY WATER REVIEW Approved
12/18/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/18/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Determine if the suite has a return air plenum.
12/18/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Need last approved site plan
2. Need to clarify second exis through labeled storeroom or confirm sprinkler system installed.
12/18/2009 PAUL MACHADO ENGINEERING REVIEW Approved
12/18/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Indicate the piping materials to be used. If the suite has a return air plenum, materials not having a flame spread/smoke developed rating of 25/50 or less cannot be used.
2. Provide a water hammer arrestor for the washer wall box.
12/18/2009 DAVE MANN FIRE REVIEW Denied Fire comments:

Exits must be 1/2 the diagonal distance apart and not through storage.
12/18/2009 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
12/18/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/18/2009 RONALD BROWN ZONING HC REVIEW Passed