Permit Number: T09CM03347
Parcel: 13338005E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03347
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A5; ELEVATION 3: WORK SURFACE AREAS MUST MEET IBC SECTION 1109.11 FOR ACCESSIBILITY.
2. SHEET A5.1; ELEVATIONS 14, 15, AND 16: SEE NOTE 1.
3. SHEET A6; PLAN 1: PROVIDE CRITICAL DIMENSIONS ON THE PLAN FOR ACCESSIBILITY PER ICC/ANSI A117.1-2003.
4. SHEET A6; DETAIL 5: INDICATE THE VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 604.5.1.
12/21/2009 ROBERT SHERRY WATER REVIEW Approved
12/21/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/21/2009 DAVE MANN FIRE REVIEW Approved
12/21/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical Plan Check: Please review the following and
resubmit.
1. Circuit P2-30 is shown on the panel schedule, cannot find on the power plan.
2. Since new outdoor lighting is added,show compliance with Outdoor Lighting Code # 10135.

Ray T Majuta, Elect Pln Ck
PDSD City of Tucson,
12/21/09
520/837/4988
12/21/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations to include the occupancy types shown in Table 403.3, IMC 2006. Reference: Sections 403.3 and 403.3.2, IMC 2006
12/21/2009 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
12/23/2009 CPIERCE1 WWM REVIEW Needs Review