Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM03347
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/21/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A5; ELEVATION 3: WORK SURFACE AREAS MUST MEET IBC SECTION 1109.11 FOR ACCESSIBILITY. 2. SHEET A5.1; ELEVATIONS 14, 15, AND 16: SEE NOTE 1. 3. SHEET A6; PLAN 1: PROVIDE CRITICAL DIMENSIONS ON THE PLAN FOR ACCESSIBILITY PER ICC/ANSI A117.1-2003. 4. SHEET A6; DETAIL 5: INDICATE THE VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 604.5.1. |
12/21/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/21/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
12/21/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
12/21/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical Plan Check: Please review the following and resubmit. 1. Circuit P2-30 is shown on the panel schedule, cannot find on the power plan. 2. Since new outdoor lighting is added,show compliance with Outdoor Lighting Code # 10135. Ray T Majuta, Elect Pln Ck PDSD City of Tucson, 12/21/09 520/837/4988 |
12/21/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
12/21/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations to include the occupancy types shown in Table 403.3, IMC 2006. Reference: Sections 403.3 and 403.3.2, IMC 2006 |
12/21/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
12/23/2009 | CPIERCE1 | WWM | REVIEW | Needs Review |