Permit Number: T09CM03305
Parcel: 132130800

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM03305
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2010 ROBERT SHERRY WATER REVIEW Passed
01/05/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/05/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify how the secondary (overflow) drains are to be installed in the canopy and how they were sized. Reference: Sections 103.2.3 and 1101.11.2, UPC 2006
2. Provide a cleanout at the base of each roof drain leader prior to its connection with the horizontal storm drain. Reference: Section 1101.12.2, UPC 2006.
01/08/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM03305
3434 S Kino Pwy
Cosco Gas Station

The electrical plans have been denied for the following:

1. Commercial Submittal Requirements per City Tucson PDSD state plans including Hazardous Locations to be sealed by Arizona EE.
2. Check with utility rep, the conduit between utility transformer and this new service to be min-2 1/2'' conduit, and equipment grd not used.
3. Show compliance according to the City of Tucson Outdoor Lighting Ord #10135.

Ray T Majuta
Elect Pln Ck,PDSD,City of Tuc.,
1/12/10
Ray.Majuta@tucsonaz.gov
01/11/2010 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Cosco 3434 S. Kino Pkwy
T09CM03304 & T09CM03305
Building Plan (1st Review)

TRANSMITTAL DATE: January 11, 2010

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans appear to be in compliance with the last submitted Development package. At this time the Development package has not been approved by all PDSD agencies therefore zoning cannot approve the building plants.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm03304.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
01/14/2010 ELIZABETH LEIBOLD ENGINEERING REVIEW Denied Submit copy of approved planview sheets from approved Development Plan.
12/17/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET AG-4; DETAIL 12: PROVIDE WET STAMPED STRUCTURAL CALCULATIONS OF THE CONTROLLER ENCLOSURE.
2. SHEET AG-4: PROVIDE WET STAMPED STRUCTURAL CALCULATIONS OF THE CONTROLLER ENCLOSURE FOUNDATIONS.
3. SHEET AG-4: PROVIDE THE TOP ELEVATION OF THE CONTROLLER ENCLOSURE (HEIGHT ABOVE THE CONCRETE SLAB).
4. GENERAL: ALL LETTERING MUST BE A MINIMUM OF 3/32" IN HEIGHT (SHEET S-1).
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/17/2009 DAVE MANN FIRE REVIEW Approved
12/18/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
12/22/2009 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2010 CPIERCE1 OUT TO CUSTOMER Completed
02/02/2010 SUE REEVES REJECT SHELF Completed