Permit Number: T09CM03304
Parcel: 132130730

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T09CM03304
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/20/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/22/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/10/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied 1) PP SE-1 DOES NOT CONTAIN CLOUDING INDICATING CHANGES BUT HAS BEEN REVISED FROM LAST APPROVED PLAN.

1A) PLEASE CLARIFY WHERE THE 3 ADDITONAL ACRES OF LAND ARE WHICH WERE USED FOR THE OUTDOOR LIGHTING CALCULATIONS.

1B) PLEASE INDICATE WHERE ALL ADDED LIGHTING IS LOCATED.

2) PP E-1 HAS BEEN ALTERED WITHOUT CLOUDING CHANGES. PLEASE PROVIDE CUT SHEETS FOR NEWLY INDICATED "NIGHT VISION" FIXTURE TYPE "F" AND INFORMATION FOR FIXTURE TYPE "F1" NOTED ON PP SE-1.

3) PP E-8 PANEL HB DOES NOT APPEAR TO HAVE BEEN CHANGED FOR THE ADDITONAL LIGHTING SPECIFIED ON PP SE-1.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/19/2010 SUE REEVES OUT TO CUSTOMER Completed
11/19/2010 GERARDO BONILLA REJECT SHELF Completed