Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM03304
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/17/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED TO SHOW LOCATION & METHOD OF CONNECTION TO PUBLIC SEWER FOR ENTIRE SITE(THE BRIDGES-BLOCK 1-16) NEED TO PERMIT ON-SITE PRIVATE SEWER. NEED COPY OF ON -SITE PRIVATE SEWER. NEED DEQ REVIEW & APPROVAL TO CONSTRUCT ON-SITE PRIVATE SEWER. NEED WASTEWATER/ INDUSTRIAL CONTROL REVIEW & APPROVAL OF FOOD SERVICE/ TIRE INSTALL/ PHOTO CENTER- tON TOMCHAK 443-6200 5025 W INA RD |
| 02/18/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/19/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 02/24/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/26/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: Costco, T09CM03304 3434 S Kino Wy The City Of Tucson Outdoor lighting Code #10135, has not been addressed properly. 1. Not all outdoor light fixtures have been included on the lumen count. All L type fixtures omitted. These fixtures do not appear to meet the definition of a Full Cut Off Light Fixture, as described in the ordinance. On Sheet SE-1, it is noted that "No unshielded fixture is being used." If a fixture is not Full Cut Off, it is unshielded. The notes in table 401.1 of the Ordinance indicate unshielded fixtures can only be 3000 lumens. Verify on plan 2. The L type fixtures under the canopy need not be included in the lumen count if Full Cut Off, please verify this on plan. Ray T Majuta, Elect Plan Review, PDSD, City Of Tucson, Ray.Majuta@tucsonaz.gov |
| 03/02/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Provide information to show that the refrigeration systems being installed comply with the requirements of Chapter 11, IMC 2006. |
| 03/03/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Based on the information shown on sheet C-2.2 (seal dated 2/5/10), the rim elevation of private sanitary manhole MH#5 (2498.04) is less than 12" below the first floor elevation (2499.00). Provide backwater valves for building sewer connections located between MH#4 and MH#5, per Section 710.1, UPC 2006, as amended by the City of Tucson (or lower MH#5 by 0.04 feet). 2. The manufacturer's data sheet for the Kay Chemical detergent injection system shows an air gap located within the confines of the dispenser unit. Air gaps that are permanent parts of a listed assembly but do not conform to the requirements of Table 6-3, UPC 2006 can be approved if they have been tested under actual backflow conditions with vacuum levels of 0 to 25 inches of mercury. Provide listing data to show that the unit has been tested for these conditions. Reference: Section 603.1 and footnote 4, Table 6-3, UPC 2006. 3. Correct the branch piping sizes called out for the flush valves (1" for the water closets and ¾" for the urinals) as shown in detail 27/P-2.1 and unisex restroom (146) on sheet P-2.1. Reference: Section A 6.1, UPC 2006 and IS 3-2003, Section 2.6. 4. Revise the size of the proposed scuppers for roof areas larger than 8373 square feet to comply with the requirements of Section 1101.11.2.1, UPC 2006. 5. Food preparation sinks, sinks used in direct contact with ready-to-eat food, sinks used for sterile materials, and the sanitizing compartments of ware-washing or pot-washing sinks shall have indirect waste connections. All other sinks and sink compartments shall be directly connected to the building drain system in accordance with the Uniform Plumbing Code. Reference: Sections 304.0, 801.2, and 806.0, UPC 2006. 6. Water heaters WH-10 and WH-11 are storage-type units and will require the installation of thermal expansion tank or other approved device to allow for the expansion of the water. Reference: Section 608.3, UPC 2006. 7. Temperature and pressure relief piping shall not terminate into a water heater pan (detail 16/P-4.2). Reference: Section 508.5, UPC 2006. 8. Provide a cleanout at the base of each roof drain leader prior to its connection with a horizontal storm drain. Reference: Section 1101.12.2, UPC 2006. |
| 03/05/2010 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Denied | Grading Plans must be ready for issuance prior to approval of building plans. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/16/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 03/16/2010 | SUE REEVES | REJECT SHELF | Completed |