Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM03304
Parcel: 132130730

Review Status: Completed

Review Details: OTHER

Permit Number - T09CM03304
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Condensate drains may not terminate with a direct connection to a rain water leader. Condensate drains may terminate over a roof drain or gutter if the roof drain or gutter terminates at or above grade in an area capable or absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson and Sections 311.4 and 807.2, UPC 2006.
2. Provide calculations demonstrating adequate ventilation. Reference: Sections 401.2, 403.3, and 403.3.2, IMC 2006.
3. The 2006 International Energy Conservation Code with Local Amendments is the relevant energy code for this project.
4. Provide information to show that the operation of the Type I hoods and the hood exhaust fans comply with Section 507.2.1.1, IMC 2006.
5. Provide the listing information for the pizza oven hood and for the rotisserie hood with regard to the back clearances shown in details 1/M-2.2 and 2/m-4.1. Reference: sections 106.3.1 and 308.2, and 507.9, IMC 2006.
6. Provide information to show that the refrigeration systems being installed comply with the requirements of Chapter 11, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2010 SUE REEVES OUT TO CUSTOMER Completed