Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM03280
Parcel: 126170840

Address:
3916 E HAYNE ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T09CM03280
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2010 RONALD BROWN BUILDING-RESIDENTIAL REVIEW Denied 1. The minimum lettering size is 3/32". Your BRACED WALL PANEL SCHEDULE on sheets A-4 and A-5 are well below that size. Please revise height of letters.
SITE PLAN
2. Please show location of utility lines from meters and from property line to building, R106.1.1.
FOUNDATION PLANS
3. Please note grade away from foundations shall fall min 6" within the first 10’, R401.3.
4. Please provide a landing or floor surface at all new master bedroom doors to the outside, R311.4.3.
STRUCTURAL FRAMING PLANS
5. Please specify design criteria on plans. Provide values for floor/roof dead and live loads.
6. Please provide a roof plan showingh location and sizes of roof drains/scuppers, UPC chapter 11.
ELEVATIONS
7. Specify height above grade for finished floor, windows, doors, exterior walls, rooflines, porches, chimneys, etc.
SECTIONS AND DETAILS
8. Please specify wall and ceiling covering. Note: Ceiling gypsum board must be either 5/8" or ½" sag resistant
when applied to ceilings framed at 24" o/c, IRC table R702.3.5 footnote d.
ELECTRICAL PLANS
9. Provide an acurate electrical riser diagram with grounding method and bonding to metallic piping, E3303, E3507. Show an AERIAL service entrance with weatherhead stand pipe on the Riser Diagram. The riser show here does not reflect the actual conditions. The site plan labels the replacement panel as a junction box which it is not.
10. Provide riser diagrams for sub-panels with feeder conductors, conduit sizes, and over-current protection (with appropriate correction factors), E3605.5.
11. Provide feeder load calculations for sub-panels (40% demand factor may not be applied), E3604.
12. Provide a panel schedule for the new 100a sub-panel : panel size, circuit numbers, ampacity, and wire sizes, E3304.11, E3606.2.
13. Indicate location of all mechanical equipment disconnect switches, E4001.5. Master Bedroom HVAC equipment and existing toilet room exhaust fan are not shown.
14. Bedroom outlets shall be arc-fault protected (receptacles, lights, and smoke detectors), E3802.12.
PLUMBING PLANS
15. Plumbing shall comply with 2006 UPC with state amendments (AZ State plumbing code). The plans should reference this code, or appeal to the Building Official for alternate design approval.
16. Provide the maximum developed length of water line from the meter the furthest appliance served, and
the diameter of the water line, UPC Table 6-6.
17. Provide location of hose bibs and note the requirement of backflow preventers, UPC 603.
18. Provide a gas line isometric and size the supply pipe for the connected demand. Include the length of
line and BTU demand for each appliance, size of each branch, total demand, and total developed
length from meter to the most remote appliance on the system, UPC 1217.0 Table 12-8. Show on site plan.
MECHANICAL PLAN
19. Show the condensate line and secondary for HVAC unit, M1411.3.
20. Gas appliances shall comply with ARIZONA STATE PLUMBING CODE combustion air
requirements or Chapter 17, 2006 IRC. Show compliance for all appliances. Confined spaces require
a minimum of two 100 SQ. IN. openings, M1702.2.
21. Show a minimum 2’ termination above any roof point within 10’ measured horizontally and not less
than 3’ above the point where a chimney (metal pipe) passes through the roof, G2427.5.3.
OUTDOOR LIGHTING CODE
22. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture
wattage. All other fixtures are assumed to be unshielded (non-FCO style).
23. Provide a note requiring the insulation certificate shall be posted in the electrical distribution panel
before final inspection, N1101.8.
FLOOR PLAN
23. Show wall mounted HVAC unit on floor plan and electrical plan.
END OF REVIEW
12/17/2009 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/22/2010 DELMA ROBEY OUT TO CUSTOMER Completed
01/22/2010 SUE REEVES REJECT SHELF Completed