Permit Number: T09CM03279
Parcel: 13623009B

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM03279
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2009 RBROWN1 FIRE REVIEW Needs Review
12/14/2009 RONALD BROWN ADA REVIEW Passed
12/14/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Needs Review
12/14/2009 RONALD BROWN ZONING HC REVIEW Needs Review
12/14/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
12/16/2009 STEVE SHIELDS ZONING REVIEW Approved
12/16/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/22/2009 ROBERT SHERRY WATER REVIEW Approved
12/22/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/22/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the ventilation requirements for the "kitchenette" with regard to Table 6-1, ASHRAE 62.1-2004.
2. Revise the zone air distribution effectiveness from 1 to 0.8 for the gas-fired A/C units.
3. The minimum duct insulation shall be R4.2.
4. Provide energy code compliance calculations using the correct climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
12/24/2009 DROBEY1 WWM REVIEW Needs Review
12/24/2009 DROBEY1 PLUMBING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/24/2009 DELMA ROBEY APPROVAL SHELF Completed
12/24/2009 DELMA ROBEY OUT TO CUSTOMER Completed
12/24/2009 DELMA ROBEY REJECT SHELF Completed