Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM03278
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/06/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the make up air duct within 18" of the Type I exhaust hood complies with the requirements of Section 506.3.1.2, IMC 2006. 2. Specify the Type I hood to be installed (i.e. if the U.L. 710-listed CaptiveAir hood shown on the attached shop drawings is to be installed, state that). Reference: Sections 106.3.1 and 507.1 (1), IMC 2006. 3. Specify the dimensions of the grease exhaust duct. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson. 4. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006. 5. Revise detail 6/M2 to be more specific regarding the type of roof structure to which the load is being attached and the Unistrut fitting being used (i.e. model number). Reference: Section 106.3.1, IMC 2006. 6. Coordinate the specifications for the proposed grease duct insulation system as shown on sheet M4 and detail 4/A2. The use of ESR-1255 does not comply with the 2006 IMC. Reference: Section 506.3.10 (1), IMC 2006. |
| 01/07/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/15/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/15/2009 | RONALD BROWN | ADA | REVIEW | Passed | Not a COT owned/operated property |
| 12/17/2009 | RONALD BROWN | ZONING HC | REVIEW | Denied | 1. Detail 3A-1: a. Provide a vertical grab bar as per ICC (ANSI) 117.1, Section 604.5.1 b. Several dimensions are incorrect, please correct to comply with ICC (ANSI) 117.1, Section 604.3 Clearances c. Reference fixture 16 to Front Elevation-Toilet. END OF REVIEW |
| 12/17/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Building Occupancy is not "M" as noted. Please revise Building Occupancy to "A-2" Restaurant as per the 2006 IBC, Section 303.1 2. Occupancy Load of 91 is not consistant with seating layout and kitchen size of detail 1/A-1. Please recalculate as to an A-2 Occupancy and/or fixture layout. 3. Please provide structural calculations and structural detail support of kitchen exhaust hood. 4. Show interior partition support to strucrure to show compliance with 2006 IBC, Section 1607.13, min 5psf horizontal load. 5. Provide previously approved site plan. END OF REVIEW |
| 12/29/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/31/2009 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 12/31/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | Remove the flow control device from the 3-compartment sink; the building has been provided with a gravity grease interceptor. A flow control device is not required and only serves as an obstruction to the waste flow. Reference: Sections 311.5 and 1014.3, UPC 2006. Contact Industrial Wastewater Control (443-6200) to determine if additional fixtures must be connected to the gravity grease interceptor. Approval of the plans by the Pima County Health Department is required prior to approval from the City of Tucson. Provide a floor drain in the kitchen scullery area. Reference: Sections 411.2.2 and 704.3, UPC 2006. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Specify the type of backflow prevention device required for each water connection. Reference: Section 603.0, UPC 2006, as amended by the City of Tucson One of the specified fixtures (American Standard water closet) requires a minimum pressure greater than the 15-PSI used in the water pipe sizing calculations. Revise calculations as necessary. Reference: Section 608.1, UPC 2006. Include all fixtures when calculating the total demand and determining pipe sizes. Reference: Section 610.1, UPC 2006. |
| 12/31/2009 | RMYERS1 | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/07/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 01/07/2010 | SUE REEVES | REJECT SHELF | Completed |