Permit Number: T09CM03278
Parcel: 137055270

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03278
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/06/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the make up air duct within 18" of the Type I exhaust hood complies with the requirements of Section 506.3.1.2, IMC 2006.
2. Specify the Type I hood to be installed (i.e. if the U.L. 710-listed CaptiveAir hood shown on the attached shop drawings is to be installed, state that). Reference: Sections 106.3.1 and 507.1 (1), IMC 2006.
3. Specify the dimensions of the grease exhaust duct. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson.
4. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
5. Revise detail 6/M2 to be more specific regarding the type of roof structure to which the load is being attached and the Unistrut fitting being used (i.e. model number). Reference: Section 106.3.1, IMC 2006.
6. Coordinate the specifications for the proposed grease duct insulation system as shown on sheet M4 and detail 4/A2. The use of ESR-1255 does not comply with the 2006 IMC. Reference: Section 506.3.10 (1), IMC 2006.
01/07/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/15/2009 DAVE MANN FIRE REVIEW Approved
12/15/2009 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
12/17/2009 RONALD BROWN ZONING HC REVIEW Denied 1. Detail 3A-1:
a. Provide a vertical grab bar as per ICC (ANSI) 117.1, Section 604.5.1
b. Several dimensions are incorrect, please correct to comply with ICC (ANSI) 117.1, Section 604.3 Clearances
c. Reference fixture 16 to Front Elevation-Toilet.

END OF REVIEW
12/17/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Building Occupancy is not "M" as noted. Please revise Building Occupancy to "A-2" Restaurant as per the 2006 IBC, Section 303.1
2. Occupancy Load of 91 is not consistant with seating layout and kitchen size of detail 1/A-1. Please recalculate as to an A-2 Occupancy and/or fixture layout.
3. Please provide structural calculations and structural detail support of kitchen exhaust hood.
4. Show interior partition support to strucrure to show compliance with 2006 IBC, Section 1607.13, min 5psf horizontal load.
5. Provide previously approved site plan.

END OF REVIEW
12/29/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
12/31/2009 GERRY KOZIOL WWM REVIEW Passed
12/31/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied Remove the flow control device from the 3-compartment sink; the building has been provided with a gravity grease interceptor. A flow control device is not required and only serves as an obstruction to the waste flow. Reference: Sections 311.5 and 1014.3, UPC 2006.
Contact Industrial Wastewater Control (443-6200) to determine if additional fixtures must be connected to the gravity grease interceptor.
Approval of the plans by the Pima County Health Department is required prior to approval from the City of Tucson.
Provide a floor drain in the kitchen scullery area. Reference: Sections 411.2.2 and 704.3, UPC 2006.
Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Specify the type of backflow prevention device required for each water connection. Reference: Section 603.0, UPC 2006, as amended by the City of Tucson
One of the specified fixtures (American Standard water closet) requires a minimum pressure greater than the 15-PSI used in the water pipe sizing calculations. Revise calculations as necessary. Reference: Section 608.1, UPC 2006.
Include all fixtures when calculating the total demand and determining pipe sizes. Reference: Section 610.1, UPC 2006.
12/31/2009 RMYERS1 WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/07/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
01/07/2010 SUE REEVES REJECT SHELF Completed