Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM03277
Parcel: 13215001B

Address:
705 E AJO WY

Review Status: Completed

Review Details: OTHER

Permit Number - T09CM03277
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/18/2009 GERRY KOZIOL WWM REVIEW Approved
12/18/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/31/2009 SUE REEVES APPROVAL SHELF Completed
12/31/2009 CPIERCE1 OUT TO CUSTOMER Completed