Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM03276
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/14/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/14/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide sealed design documents. 2. Show that the rooms being modified have adequate ventilation. Reference: section 401. IMC 2005. 3. Show the termination points for the condensate drains. |
| 12/14/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T09CM03276 TI Office 283 N Stone The Electrical Plans must be sealed by an EE. Ray Majuta Elect Pln CK PDSD City of Tuc 12/14/09 Ray.Majuta@tucsonaz.gov |
| 12/14/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/14/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Need structrural calculations for new HVAC units on roof |
| 12/14/2009 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures |
| 12/14/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/14/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 12/14/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/14/2009 | RONALD BROWN | ADA | REVIEW | Passed | |
| 12/14/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/14/2009 | RONALD BROWN | ZONING HC | REVIEW | Approved |