Permit Number: T09CM03271
Parcel: 14043011A

Address:
6901 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03271
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2009 MICHAEL ST. PAUL ZONING REVIEW Passed
12/11/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/14/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM03271

Call out lighting circuits,provide panel designation,and load in panel schedule.
2. Finish total load calculations for panel A.

Ray T Majuta
Elect Pln CK
12/14/09
520/837/4988
12/14/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/14/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Need structural calculations for replacement of HVAC units on roof.
2. Reclassify hanger as H-2 Aircraft Hanger Repair.
3. Verify fire rating of wall separating offices. It must be 3 hour as per table 508.3.3. Modify wall as required to meet fire rating requirements.
4. Confirmm window existing and new, fenistration rating in fire separation wall.
12/14/2009 ROBERT SHERRY WATER REVIEW Approved
12/14/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The T&P relief pipe shall not be combined with the water heater pan drain.
2. Provide a light source for the water heater area above the ceiling.
12/14/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/14/2009 RONALD BROWN ADA REVIEW Passed
12/14/2009 RONALD BROWN ZONING HC REVIEW Denied 1. Provide a compliant water cooler.
2. Lavs must be 2'-10" a.f.f.
3. Provide dim ensions for accessible accessories, grad bars, etc.
END OF REVIEW
12/31/2009 GBONILL1 WWM REVIEW Needs Review
12/31/2009 GBONILL1 FIRE REVIEW Needs Review