Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM03266
Parcel: 11451216G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03266
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
12/11/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/11/2009 ERIC NEWCOMB ADA REVIEW Passed
12/11/2009 ROBERT SHERRY WATER REVIEW Approved
12/11/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/11/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/11/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A bottled water unit is not a substitute for either a drinking fountain or a point-of-use water dispenser. Provide a water fountain that complies with Section 1109.5 and Table 2902.1, IBC 2006, or a point-of-use water dispenser (connected to potable water) with a disposable cup dispenser mounted at an accessible height.
2. Show how the new plumbing relates to the existing plumbing and show that it does not overload the capacity of the existing plumbing. Reference: Sections 101.5.1 and 103.2.3, UPC 2006.
3. Provide a cleanout for the new mop sink. Reference: Section 707.4, UPC 2006.
12/11/2009 MARTIN BROWN FIRE REVIEW Approved
12/11/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
12/11/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/15/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical comments:Denied for the following,--
How will switching requirements indicated on the Interior Lighting Compliance Report be made, show on plan.

Ray T Majuta
Electrical Plan Ck
PDSD City of Tucson
12/15/09
Ray.Majuta@tucsonazx.gov
12/23/2009 GERRY KOZIOL WWM REVIEW Approved