02/16/2010 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 2-16-10
Activity: T09CM03265
Address: 5738 S Southland Blvd
Applicant: Jesus Rodriguez Jr

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

STRUCTURAL / FRAMING PLAN:
2. Justify the roof framing design under the proposed mechanical unit, R801.2.
3. Justify the 4x10 beam size at the opening between existing and new living areas, R801.2.

PLUMBING PLAN:
4. Provide a water fixture unit schedule that includes the combined value for hot and cold supply, for the entire property (including existing) P2903.6.
5. Provide the maximum developed length of water line from the meter the furthest appliance served, and the diameter of the water service line, P2903.7.

MECHANICAL PLAN:
6. Show supply and return air ducts with a minimum R-8 insulation when located outside the thermal envelope, R1103.2.1.