Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fan to operate whenever air is being supplied to the restroom so that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006

Final Status

Task End Date Reviewer's Name Type of Review Description
01/21/2010 CINDY AGUILAR OUT TO CUSTOMER Completed