Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T09CM03252
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fan to operate whenever air is being supplied to the restroom so that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/21/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |