Permit Number: T09CM03252
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03252
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/10/2009 JASON GREEN ENGINEERING REVIEW Approved
12/10/2009 ERIC NEWCOMB ADA REVIEW Passed
12/10/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/10/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
12/11/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference: Section 401.2, IMC 2006.
2. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006
12/11/2009 TERRY STEVENS ZONING REVIEW Approved
12/11/2009 ROBERT SHERRY WATER REVIEW Approved
12/11/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/11/2009 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
12/11/2009 MARTIN BROWN FIRE REVIEW Approved
12/11/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed