Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM03230
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/06/2010 | RONALD BROWN | BUILDING-RESIDENTIAL | REVIEW | Denied | 1. Clarify the use of a 4" square column to support the 3-2x12 ridge beam. 2. A 1" water line is shown as the service line to the new addition whereas the site plan deplicts a 1 1/4" line. Please clarify. 3. As per previous comments, please specify the size of the existing water meter. END OF REVIEW |