Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2010 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 2-23-10
Activity: T09CM03230 2nd Review
Address: 4155 E Kilmer St
Applicant: David Woodruff

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

STRUCTURAL / FRAMING PLAN:
2. Justify the proposed double 2x12 ridge beam for the intended span, R801.2. (The ridge must be sized for a beam load with the proposed design)

PLUMBING PLAN:
3. Specify the size of the existing sewer to be tapped and the number of water closets in the existing building, UPC Table7-5 footnote 4. (The connection of four water closets to a sewer line requires a minimum 4" diameter pipe)
4. Specify the size of the existing water supply line to the building and the size of the existing water meter, UPC Table 6-6. (The water supply line must be sized to accommodate the proposed demand)