Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM03210
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03210
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2009 TERRY STEVENS ZONING REVIEW Approved
12/08/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 (not the ASHRAE 62-2001) ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used.
2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. The minimum insulation for ducts located in indirectly conditioned spaces within the building envelope is R-4.2 (installed). Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
3. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or above grade in an area capable or absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
12/08/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/08/2009 ROBERT SHERRY WATER REVIEW Approved
12/08/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Needs Review
12/08/2009 GERRY KOZIOL WWM REVIEW Approved
12/08/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC.
2. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
4. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
12/08/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/08/2009 DAVE MANN FIRE REVIEW Approved
12/08/2009 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
12/08/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/08/2009 RONALD BROWN ZONING HC REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2009 DELMA ROBEY OUT TO CUSTOMER Completed