Permit Number: T09CM03187
Parcel: 114600330

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM03187
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/04/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
12/04/2009 PAUL MACHADO ENGINEERING REVIEW Approved
12/04/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved Plans denied for the following:

1. Service grounded conductor to be sized per 2005 NEC 230.31(C)

2. Min Rating for service disconnect to be per NEC 2005 230.79(D)

3. Disconnect to be sutiable for use as service equipment 2005 NEC 230.70(C)

Rich Jiroudek
Electric Plans Examining