Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T09CM03187
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/04/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/04/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/04/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 12/04/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Plans denied for the following: 1. Service grounded conductor to be sized per 2005 NEC 230.31(C) 2. Min Rating for service disconnect to be per NEC 2005 230.79(D) 3. Disconnect to be sutiable for use as service equipment 2005 NEC 230.70(C) Rich Jiroudek Electric Plans Examining |