Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T09CM03178
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/23/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/23/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | Provide specifications for the gas-fired space heaters. |
| 12/23/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | 1. Clarify the gas piping design. No gas loads are shown for the space heaters and gas (of unknown quantity) is being supplied to a heat pump which doesn't require gas service according to the mechanical schedule. 2. Clarify the waste piping for the bar area on the 2nd floor. The riser diagram appears to show the dishwasher and the underbar handsink with direct-connections, and waste lines connecting to trap arms that have no vents. 3. Fixtures P2, P5, and P6 on the 2nd floor do not appear to have any connection to the drain system. |
| 12/23/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 12/24/2009 | LHANLY1 | WATER | REVIEW | Approved | |
| 12/24/2009 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/24/2009 | LHANLY1 | WWM | REVIEW | Passed | MINOR RELOCATION OF EXISTING WET BARS |
| 12/24/2009 | CRAIG GROSS | ZONING | REVIEW | Approved | |
| 12/29/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 12/29/2009 | DAVE MANN | FIRE | REVIEW | Approved |