Permit Number: T09CM03173
Parcel: 126122680

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03173
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2009 STEVE SHIELDS ZONING REVIEW Approved
12/03/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify operation of the restroom exhaust fans.
2. Coordinate the airflow quantities shown for each A/C unit.
3. Exhaust air quantities from each restroom shall be greater than or equal to the supply air quantities.
12/03/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
12/03/2009 ROBERT SHERRY WATER REVIEW Approved
12/03/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/03/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the meaning of "as necessary" in detail 2/P1.0.
2. Clarify the intent of the connection note for P-6.
12/03/2009 DAVE MANN FIRE REVIEW Denied Fire Comments:
Rated corridors are required per IFC Section 1017.
12/03/2009 ERIC NEWCOMB ADA REVIEW Passed
12/03/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/03/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
12/04/2009 DROBEY1 WWM REVIEW Needs Review
12/04/2009 DROBEY1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2009 DELMA ROBEY OUT TO CUSTOMER Completed