Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03163
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2009 STEVE SHIELDS ZONING REVIEW Approved
12/02/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a mechanical plan and ventilation calculations for the new areas.
12/02/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Plans denied for the following:

1. Show existing panel ratings. Include amp rating along with feeder size and rating.
2. Provide panel directory include existing loads with new loads.
3. Provide ratings of new instahots.

Rich Jiroudek
Electric plns examing
12/02/2009 ROBERT SHERRY WATER REVIEW Approved
12/02/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/02/2009 JASON GREEN ENGINEERING REVIEW Approved
12/02/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide fixture descriptions for all plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, NSF, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006.
2. Provide equipment descriptions and electrical specifications for the proposed water heaters.
12/02/2009 MARTIN BROWN FIRE REVIEW Approved
12/02/2009 RONALD BROWN ADA REVIEW Passed
12/02/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/02/2009 RONALD BROWN ZONING HC REVIEW Approved
12/14/2009 CAGUILA1 WWM REVIEW Needs Review