06/23/2010 MARTIN BROWN FIRE REVIEW Approved
06/24/2010 JASON GREEN ENGINEERING REVIEW Denied DATE: June 24, 2010
SUBJECT: 3607 E Speedway Blvd- Revised Site and Grading Plan
TO: Seaver Franks Architects
LOCATION: T14S R14E Sec04 Ward 6
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM03157 (Site Plan), T09BU01778 (Grading Plan) and T10OT00094 (Floodplain Use Permit)


SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the revised site plan (T09CM03157) and grading plan (T09BU01778) for the above referenced property. Engineering Division does not recommend approval of the site plan or grading plan at this time.

SITE PLAN COMMENTS: The following comments or from the 3rd revision review. Revision reviews #1 and 2 (under the same revision folder in Permits Plus) were completed at the counter with the applicant and corrections were redlined on the plan. The following comments still need to be addressed prior to site plan approval:

1) Revise Sheet 1 to correctly show the improvements as proposed on Sheet 2. For example Sheet 2 has revised the 18-foot radii for the north PAAL to a standard driveway apron detail and one of the refuse container locations has been removed, Sheet 1 should reflect these revisions.

2) Provide a new detail on Sheet 3 to correctly show the new 24' sliding gate detail. The 18-foot radii are no longer applicably due to the proposed standard driveway aprons therefore the detail must be revised to reflect what is proposed.

3) Verify that all 3 sheets of the proposed site/grading plan match each other for the proposed improvements (i.e. revised sidewalk location, removal of refuse container, standard driveway aprons, etc.).


GRADING PLAN:

4) The grading plan (T09BU01778) application will be stamped approved with the site plan once all comments have been addressed.


GENERAL COMMENTS:

Please provide a revised site plan and grading plan set that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package.

Further comments may be generated upon resubmittal of the plan review.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Planning & Development Services
06/28/2010 ANDREW CONNOR NPPO REVIEW Passed
06/28/2010 ANDREW CONNOR LANDSCAPE REVIEW Passed
06/30/2010 STEVE SHIELDS ZONING REVIEW RECEIVED PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: James Autosports
T09CM03157
Site Plan (Revision #1)

TRANSMITTAL DATE: June 30, 2010

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance the proposed parking restripe and site modifications only. Per the Zoning Administrator this is not an expansion of vehicle use area or site area.

2. As sheet C2 will be combined with sheets C1 & C3 the site plan shown on sheet C1 & C2 need to match. Revise sheet C1 to match the changes to sheet C2

3. Based on the changes to the site plan there are 48 vehicle parking spaces shown. Revise the vehicle parking space calculation to match the number provided.

4. At both entrance parking area access lanes (PAALs), off of Richey Blvd, there is a 24' dimension string that does not line up with the PAALs, relocate the dimension string or clarify what the string is for.

5. Clarify what the "5'" note and arrow shown at the northern most entrance PAAL, off of Richey Blvd, is for.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t09cm03157

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan
07/13/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location of the main water lines
b. the location and size of the public sanitary sewer
c. the location of the building connection to the public sewer
d. the location, invert, and rim elevation of all manholes and cleanouts
Reference: City of Tucson Development Standard No. 2-01.1.0 2 3.8 D and Section 103.2.3, UPC 2006.
07/14/2010 RONALD BROWN ZONING HC REVIEW Denied I really can not see, from the drawings submitted as a revision, any changes from the original approved drawings in the accessible route in front of building one to the Richey public right of way. Please provide a large scale plan of the accessible route and show all changes. Please redraw this access as per approved details shown on C3.