| 08/16/2010 | ANDREW CONNOR | ZONING | REVIEW | Denied | CDRC TRANSMITTAL FROM: Michael St.Paul / Andrew Connor Planning Technician PROJECT: T09CM03134 102 East 1st Street Addition SFR TRANSMITTAL: August 16, 2010 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO). This site is located in the HR-2 Zone (LUC Section 2.3.5.2.A.1). The Development Designator is "I" (LUC Section 3.2.3.1.B) and the Perimeter Yard Indicator is AA (LUC Section 3.2.6.4). This site is located in a Historic Preservation Zone (HPZ). Historic review is required (LUC Section 2.8.8.5). The minimum setback for the proposed addition to the east side of the single-family residence (SFR) is the greater of six (6) feet or two-thirds (2/3) the height of the structure's wall facing east property line (LUC Sections 3.2.3.1.B and 3.2.6.4). The required setback to the east property line is eight (8) feet (LUC Section 3.2.6.4). The proposed setback to the east property line is 2.95 feet. |
| 08/17/2010 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/23/2010 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Approved |