Permit Number: T09CM03123
Parcel: 13419042A

Review Status: Completed

Review Details: OTHER

Permit Number - T09CM03123
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2009 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved 1) SHOW RELOCATION OF FAN OUTLETS
2) PROVIDE INFORMATION FOR ELECTRICAL INTERLOCKS AT HOOD
3) PROVIDE EXISTING PANEL SCHEDULE
11/30/2009 DAVE MANN FIRE REVIEW Approved
11/30/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the exhaust fan is to be interlocked to automatically start when cooking commences.
2. Show the size of the exhaust duct.
3. The fire suppression system will be under a separate permit.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/14/2009 CPIERCE1 OUT TO CUSTOMER Completed