Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T09CM03123
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/30/2009 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | 1) SHOW RELOCATION OF FAN OUTLETS 2) PROVIDE INFORMATION FOR ELECTRICAL INTERLOCKS AT HOOD 3) PROVIDE EXISTING PANEL SCHEDULE |
| 11/30/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/30/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the exhaust fan is to be interlocked to automatically start when cooking commences. 2. Show the size of the exhaust duct. 3. The fire suppression system will be under a separate permit. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/14/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |