Permit Number: T09CM03108
Parcel: 12701005D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM03108
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2010 STEVE SHIELDS ZONING REVIEW Approved
01/20/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM03108, Cell Site.
5151 E Broadway Bl

The plans, as they are drawn present some confusion , see following comments.

1.Where is the existing 277/480 volt panel feeding this project, and what would be the total load with this new project on it ?
2. Where is the location of Panels A and A1?
3. Sheet E-1 shows Clearwire's Manual Transfer Switch on the wall outside of the lease area, Sheet E-2 shows the Transfer Switch located in Panel A ?
4. How is Panel A1 wired from Panel A (physically) ?
5. Sheet E-2 states "Clearwire's generator plug conduit routed down along existing power conduit to Parking Garage. Show on plan where this generator plug is to be located.
6. Sheet E-2 shows the 277/480 volt panel feeding the Transfer Switch which in turn feeds Clearwire's disconnect ?
The one line diagram conflicts with this ?

Ray T Majuta,PSDS, City of Tucson,
Elect Plan Ck. 1/25/10
Ray.Majuta@tucsonaz.gov
02/11/2010 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Needs Review need form for communications

Final Status

Task End Date Reviewer's Name Type of Review Description
03/22/2010 CPIERCE1 OUT TO CUSTOMER Completed
03/22/2010 SUE REEVES REJECT SHELF Completed