| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/20/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/20/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T09CM03108, Cell Site. 5151 E Broadway Bl The plans, as they are drawn present some confusion , see following comments. 1.Where is the existing 277/480 volt panel feeding this project, and what would be the total load with this new project on it ? 2. Where is the location of Panels A and A1? 3. Sheet E-1 shows Clearwire's Manual Transfer Switch on the wall outside of the lease area, Sheet E-2 shows the Transfer Switch located in Panel A ? 4. How is Panel A1 wired from Panel A (physically) ? 5. Sheet E-2 states "Clearwire's generator plug conduit routed down along existing power conduit to Parking Garage. Show on plan where this generator plug is to be located. 6. Sheet E-2 shows the 277/480 volt panel feeding the Transfer Switch which in turn feeds Clearwire's disconnect ? The one line diagram conflicts with this ? Ray T Majuta,PSDS, City of Tucson, Elect Plan Ck. 1/25/10 Ray.Majuta@tucsonaz.gov |
| 02/11/2010 | BRIAN HEFFERNAN | COMMUNICATIONS | REVIEW | Needs Review | need form for communications |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/22/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 03/22/2010 | SUE REEVES | REJECT SHELF | Completed |