11/30/2009 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T09CM03085
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:
1. Provide consistent photo array notation. The One Line Diagram shows 4730 Watt and the Three Line Diagram shows 5805 Watt.

STRUCTURAL PLANS:
1. Provide complete roof framing information for determining load carrying capacity for each of the four arrays. Show size, spacing and span of all framing members, trusses, joists, rafters, beams, glue-lams and ledgers, R301.1. Demonstrate the ability for supporting the existing and additional dead load along with a 20 PSF live load, or show that each engineered truss receives no more than 200 pounds of additional dead loading, or provide an engineer's calculation, design and seal for verifying the truss load carrying capacity, M1401.
CALCULATIONS
1. Overcurrent protection may not exceed 30A for #10 rating required by NEC 240.4 (D).