Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM03081
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/24/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/02/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/02/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Determine the size of the waste water pipes using the fixture units shown in Table 7-3. The existing 2" drain line in room 203 has more than 8 fixture units connected to it. Reference: Section 703.1, UPC 2006 |
| 12/03/2009 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |