Permit Number: T09CM03081
Parcel: 14041015A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03081
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/25/2009 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM03081,RED CROSS

The electrical plans have been denied for the followinf:
1.Provide information on ATS, AIC rating,solid neutral, as requested last review.
2. Provide grounding electrode system on generator.
3.Sheet E-2, note #15, walkin units not shown on plan.
4. Walkin units would be MDPH circuits 14,16,18 and 20,22,24, identify on power plan
5. Mech plan shows two chilled water pumps to be installed, not shown on electrical.


Ray T Majuta
Elect Pln Ck
DPDS<City of Tucson
11/29/09
520/837/4988
12/02/2009 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
12/02/2009 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review
12/02/2009 GBONILL1 WWM REVIEW Approved approved by counnty. stamp is on plans (this entry by LeeRay)