Permit Number: T09CM03069
Parcel: 105123390

Address:
4133 N STONE AV

Review Status: Completed

Review Details: OTHER

Permit Number - T09CM03069
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2010 MARTIN BROWN FIRE REVIEW Approved
03/11/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T09CM03069
New Garage
4133 N Stone Av


Electrical Plans denied for following:

1. Change Note 1 to reflect " Electrical plans to comply with NEC 2005 and Ammendments."
2. Provide one line diagram of service feeding this new panel and identify it.
3.Provide the existing load on service feeding this new panel, and add new total for garage panel for a combined total.
4.New panel at garage is required to be grounded per NEC 250, show on plan.
5. Size feeder from existing service to new panel.
6. Provide fixture cut sheets on all fixtures.

RAY T MAJUTA, EL PLAN CK
520/837/4988

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2010 CPIERCE1 OUT TO CUSTOMER Completed